Data logger for current 0-20mA,
voltage 0-5V and binary signal
Data logger S6021, respective S5021
Main applications of data logger:
- Distant places with no electric power
- Long term field measurement
- Research and development
- Laboratories
- Technological processes
Advantages of data logger:
- included traceable calibration certificate from the manufacturer - Comet
- fast data transfer to the PC (full memory for approximately 30s)
- variability of connection to the computer - USB, RS232, Ethernet, GSM modem
- permanent connection to the PC enabled, data is possible to download even during logging
- large data memory 32000 values
- large dual line display with special symbols, switchable
- optional display of minimum and maximum measured values (reset of min/max memory from PC or by magnet)
- dual level alarm is enabled for each channel, alarm is indicated by blinking of the value on the LCD display
- two alarm modes are enabled: instant or with memory (detected alarm is indicated permanently till alarm memory is cleared)
- robust watertight case
- easy installation, locking enabled
- low power consumption from battery, battery life up to 6 years
- indication of remaining battery life, easy replacement of the battery
- logging start/stop is enabled: at certain time and date programmed from computer, by external binary signal or by delivered magnet
- also special logging mode is enabled, when logging runs only, if some of measured values are out of adjusted alarm limits
- input signal is recalculated and displayed in real measured physical units by means of the PC software
- each logger is possible to describe with text of maximum 32 characters
- each channel is possible to describe with text of maximum 16 characters
- password protection is enabled to prevent unauthorized manipulation with logger
TECHNICAL PARAMETERS | |
---|---|
Measurement accuracy: | ±0.2% FS |
Resolution of voltage input: | 13 bits (8192 levels) |
Resolution of current input: | 7900 levels |
Signal character at binary input: | from potential-less contact or two-state voltage signal |
Minimum pulse duration at binary input: | 500 ms (shorter pulses may not be recorded) |
Maximum frequency at binary input: | 0.5 Hz (i.e. maximum 5 pulses for 10 s) |
Power current through contact at binary input: | 3 uA (contact closed) |
Voltage accross open contact at binary input: | maximum 3.6 V |
Low voltage level at binary input: | 0 to +0.2 V (maximum current from the input 3 uA |
High voltage level at binary input: | +3.0 to +30 V (maximum current to the input 100 nA |
Data logging interval: | adjustable from 10s to 24hours |
Display refresh and alarm state refresh: | every 10 s |
Total memory capacity: | 32000 values (in non cyclic mode) |
Data logging modes: | noncyclic – logging stops after filling the memory cyclic – after filling memory oldest data is overwritten by new |
Operation temperature range: | -30 to +70°C |
Real time clock: | year, leap year, month, day, hour, minute, second |
Built-in connector for input signals: | Canon 9 pins, male |
Dimensions without connectors: | 93x64x29mm |
Weight including battery: | 130g |
Power: | Lithium battery 3,6V, size AA |
Typical battery life in operation from -5 to +35°C: (if often operated outside of the above temperature range battery life can be reduced to 75%) |
6 years |
Battery life in continuous on-line mode with interval 1 minute: | 4 years |
Battery life in continuous on-line mode with interval 10 seconds: | 1 year |
Protection: | IP67 - protected against influence of temporary immersion into water |
Warranty: | 2 years |
Common manual for quick start of the loggers
Accessories
Traceable calibration certificate from the manufacturer, instruction manual.
Calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
Example of calibration certificate.
No other accessory is included. For basic use it is necessary to order at minimum a COM adapter or USB adapter for communication with computer, optionally a start/stop magnet, if needed to control logging the other way than directly from computer or by external binary signal. Also connector for input signals connection is necessary to order.
Anytime it is possible to download free basic Windows program for data logger. Program enables to control all logger functions and viewing and printing of record in numerical and simple graphic format. It is possible to export recorded values to dbf or txt formats for further analysis.
OPTIONAL ACCESSORIES | ||
---|---|---|
SWR004 | Windows optional software for data logger - color printing, vertical and horizontal zooming of graphs and other functions. | |
DBL |
Database program DBL Logger Program for work with data from Comet loggers. Program enables i.a.: - To set locally the GSM modem via RS232 link by means of the QMS2901 cable. - To view selected channels from any Comet logger together with selected channels of other Comet loggers. - Measurement from different Comet devices is possible to combine in one table or graph. - To choose any time interval for analysis. - Print, export to PDF - table and graph. - uses freeware database server MySQL |
|
SW100 | CD with free PC program | |
LP002 | COM adapter for communication with personal computer via RS232 serial port | |
LP003 | USB adapter for communication with personal computer via USB port | |
LP005 |
LAN adapter - external converter for communication with the PC via Ethernet, including ac/dc adapter 230Vac/5Vdc. Exceeding of adjusted limits is alarmed by sending e-mail message or trap. More information in manual of Ethernet interface in pdf |
|
New ! Wireless communication with loggers via GSM |
||
LP004 | start/stop magnet | |
MD036 | self adhesive Dual Lock for easy installation | |
F9000 | wall holder secured against unauthorized removal | |
A4203 | spare Lithium battery 3.6V size AA | |
K0921 | watertight female connector Canon 9 pins for connection of input signals, protection IP67. | |
K0925 | female connector Canon 9 pins for connection of input signals, protection IP20. | |
K0945 |
Adapter with terminals for easy connection of input signals, protection IP20.
Adapter enables to supply connected transducers e.g. from ac/dc adapter connected via power connector. More information in manual of adapter in pdf |