Universal monitoring system MS6D, MS6R
- with configurable inputs from PC program
NEW
Monitoring system MS6D
Monitoring system MS6R for rack 19"
- Server rooms, data centers
- Food and beverages industry (HACCP)
- Pharmaceutical industry (GMP)
- Blood stations, pharmacies
- Horticulture and cultivation of plants
- HVAC - heating, ventilation, air conditioning, cooling
- Building and energy management
- Building automation
- Research and development
- Laboratories (GLP)
Main advantage - user configurable inputs from PC program without any need to open the data logger unit.
Each data logger contains 16 inputs for measurement and record of both analog and two-state values.
Each input is individually configurable from user PC program to one from 17 measuring ranges.
Also signals from sensors working on RS485 bus with ModBus or Advantech protocol can be recorded.
Universal sixteen channel data logger is designed for data acquisition from sensors of variety values, alarm state indication, optionally for control of consecutive processes.
Data is possible to download to the PC via USB, RS232, Ethernet interfaces or GSM modem for processing.
Free program for monitoring system for Windows is ready to download.

Data logger enables to:
- Configure inputs for different input signal types from the PC program.
- Individully configure each input channel for measurement, alarm evaluation and data logging , including individual logging interval for each input.
- Individually program each input channel for different modes of record (continuous record, time dependent record, record only if specified logic conditions are matched, record triggered by external signal, etc.).
- Set up to four different logic conditions for each channel to active alarm. Each condition compares measured values from inputs with set limits. It is possible to set hysteresis and delay of condition validity.
- Indicate alarm state after matching defined combination up to four alarms from any inputs.
- Activate selected relays depending on alarm states by means of output relays module.
- Receive information from monitoring system by means of SMS messages via GSM modem - actual values, alarms, memory occupation etc.
- Assign to each input channel name of actual recorded process to identify monitored object (e.g. type of monitored product). It is enabled to select this name from data logger keyboard during the operation.
Data loggers are available in two mechanical versions:
TECHNICAL PARAMETERS OF DATA ACQUISITION SYSTEM | |
---|---|
Total memory capacity: | 2MB (up to 480 000 recorded values) |
Memory type: | internal backed-up SRAM memory |
Data logging modes: |
noncyclic - logging stops after filling the memory cyclic - after filling memory oldest data is overwritten by new |
Data logging intervals: | adjustable individually for all input channels from 1 second to 24 hours |
Real time clock: | year, leap year, month, day, hour, minute, second, backed-up by Lithium battery |
AD converter resolution (analog channels): | 16 bits, conversion duration approximately 60ms/channel |
Supported interface for communication with computer: - only one interface is enabled at a time |
|
Communication speed: | 9600, 19200, 57600, 115200 Bd |
Outputs for alarm indication: |
|
Power: | 24Vdc, consumption of data logger itself approximately 80 mA |
Operating temperature range: | 0 to +50°C |
Dimensions with plugged connectors - MS6D: | 215 x 225 x 44 mm (W x D x H) |
Dimensions with plugged connectors - MS6R: | 483 x 230 x 44 mm (W x D x H) - one rack unit 1U |
Dimensions with plugged connectors without rack holders - MS6R: | 225 x 230 x 44 mm (W x D x H) |
Protection: | IP20 |
Warranty: | 2 years |
Inputs are not galvanically isolated from each other.
PARAMETERS OF CONFIGURABLE INPUTS | ||||
---|---|---|---|---|
Measured value | Accuracy | Note | ||
dc current
4 to 20 mA |
±0.1% FS (±0.02mA) | either from active source connected between COM and GND terminals or passive sensor connected between terminals +24V and COM | ||
dc voltage -10V to +10V |
±0.1% FS (±10 mV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
dc voltage -1V to +1V |
±0.1% FS (±1 mV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
dc voltage -100mV to +100mV |
±0.1% FS (±100 uV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
dc voltage -18mV to +18mV |
±0.1% FS (±18 uV) |
input resistance approximately 10 Mohms, input terminals IN and COM |
||
thermocouple K (NiCr-Ni) -200 to +1300°C |
±0.3% from reading + 1.5°C |
linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple J (Fe-Co) -200 to +750°C |
±0.3% from reading + 1.5°C |
linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple S (Pt10%Rh-Pt) 0 to +1700°C |
±0.3% from reading + 1.5°C |
linearized, cold junction compensation, input terminals IN and COM |
||
thermocouple B (Pt30%Rh-Pt) +100 to +1800°C |
±0.3% from reading + 1.0°C od +300 to +1800°C |
linearized, without cold junction compensation, input terminals IN and COM |
||
thermocouple T (Cu-CuNi) -200 to +400°C |
±0.3% from reading + 1.5°C |
linearized, cold junction compensation, input terminals IN and COM |
||
Platinum temperature sensor Pt100 -200 to +600°C |
±0.2°C od -200 to +100°C ±0.2% from reading from +100 to +600°C |
two-wire connection,
measuring current approximately 0.8mA in pulse 50ms, input terminals IN and COM |
||
Platinum temperature sensor Pt1000 -200 to +600°C |
±0.2°C od -200 to +100°C ±0.2% from reading from +100 to +600°C |
two-wire connection,
measuring current approximately 0.5mA in pulse 50ms, input terminals IN and COM |
||
Nickel temperature sensor Ni1000/6180ppm -50 to +250°C |
±0.2°C od -50 to +100°C ±0.2% from reading from +100 to +250°C |
two-wire connection,
measuring current approximately 0.5mA in pulse 50ms, input terminals IN and COM |
||
two-wire measurement of resistance 0 to 300 Ohms |
0.1% FS (±0.3 Ohms) |
measuring current approximately 0.8mA / 50ms, input terminals IN and COM |
||
two-wire measurement of resistance 0 to 3000 Ohms |
0.1% FS (±3 Ohms) |
measuring current approximately 0.5mA / 50ms, input terminals IN and COM |
||
two-wire measurement of resistance 0 to 10000 Ohms |
0.1% FS (±10 Ohms) |
measuring current approximately 0.1mA / 50ms, input terminals IN and COM |
Binary input for two-state signal |
input voltage for state "L" (IN-COM) < 0.8 V (Rin < 1 kOhm). resistance of closed contact for state "L" (IN-COM) < 1 kOhm. input voltage for state "H" (IN-COM) > 2 V. resistance of closed contact for state "H" (IN-COM) > 10 kOhm. minimum duration for sensing of change: 200ms. |
RS485IN
- input for serial signal RS485 - optionally |
E.g. data acquisition from temperature, humidity, pressure sensors Tx41x, Hx43x. input serves for reading from devices supporting protocol ModBus RTU or Advantech. Connected to terminals next to terminals for channel 15 and 16. Input can work with 16 devices. Maximum speed 115200Bd. Galvanically isolated. |
INCLUDED | OPTIONAL | INCLUDED | INCLUDED | INCLUDED |


Included Accessories:
Traceable calibration certificate from the manufacturer with declared metrological ethalon traceability in accordance with EN ISO/IEC 17025.
Calibration certificate contains calibration of 16 inputs 4-20mA, if it is not defined required configuration of inputs by the user.
If required configuration of inputs is defined by the user, calibration certificate proves calibration of inputs in accordance with this required configuration
- maximum one range for each of 16 inputs.
Calibration of other ranges is optional.
Included is also USB communication cable of approximately 1.8 meter length and free program for Windows.
Free program is available to dowload anytime. Program enables to
control all logger functions and view and print the record in numerical format.
It is possible to export recorded data to dbf or xls formats for further analysis, e.g. in MS Excel.
For work with graphs and other functions is possible to order optional program SWR006 or database program DBM MS Logger Program - see Optional Accessories.
Optional Accessories:
to monitoring system find here![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
![]() |
DIFFERENCES IN FEATURES OF DATA LOGGERS MS6D AND MS5D | ||||
---|---|---|---|---|
Feature | MS6D | MS5D | ||
Character of inputs: | inputs configurable by the user from PC program | fixed - depends of installed HW input modules | ||
Maximum measured dc current: | 20 mA dc | 5 A dc | ||
Maximum measured dc voltage: | 10 V dc | 75 V dc | ||
Most sensitive measuring range of dc voltage: | 18 mV dc | 100 mV dc | ||
Maximum measured ac voltage: | - | 50 V ac | ||
Maximum measured ac current: | - | 5 A ac | ||
Input for measurement of frequency: | - | 0 to 5 kHz | ||
Input for counting of pulses: | - | yes | ||
Possibility of galvanical isolation of inputs: |
only serial input RS485IN, analog inputs cannot be isolated |
yes | ||
SMS port for sending/reception of SMS: | included | optionally | ||
Dimensions including connectors: | 215 x 225 x 44 mm | 215 x 225 x 60 mm |