Programmable temperature transmitter for Pt1000/3850ppm with 4-20 mA output

photo of thermometer T4111

Temperature probes and transducers for Pt1000/3850ppm sensor with 4-20mA output for two-wire connection are built in a durable watertight case. Output temperature range is user adjustable. Degrees Celsius and Fahrenheit are user selectable. Large dual line LCD is an advantage. Display is possible to switch off. Computerized design ensures maximum long term stability and fail indication.

APPLICATIONS - measuring and control of temperature at:

COMMON TECHNICAL PARAMETERS
Available temperature units: degrees Celsius, Fahrenheit
Accuracy of temperature output of T0110 probe: ±0.4°C
Accuracy of temperature output of T4111 transducer: ±0.15°C plus 0.1% from adjusted output span (without temperature probe)
Temperature operating range: -30 to +80°C
Temperature operating range of LCD display: readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C
Current output - two-wire connection: 4-20mA
Output temperature range: user adjustable from the PC
Protection: IP65 electronics
Power: 9-30Vdc
Warranty: two years

Thermometer is available in the following types:

Thermometer ModelMeasured valueMaximum range of measured temperatureOutputNote

T0110

larger photo of thermometer
temperature -30 to +80°C -30 to +80°C outdoor and indoor

Mechanical drawing

Interconnection terminals

Manual in pdf
Temperature transducer - manual in pdf

T4111

larger photo of thermometer
temperature -200 to +600°C -200 to +600°C transducer for Pt1000/3850ppm probes, output range adjustable by the user

Mechanical drawing

Interconnection terminals

Manual in pdf
Temperature transducer - manual in pdf

Output is adjusted to maximum temperature range from the manufacturer.
To adjust other range by the user buying of SP003 cable is necessary - see Optional accessory.
Free configuration program TSensor for transmitter adjustment is ready to download anytime.

If different adjustment of output temperature range is required, please specify required range in the order. Adjustment is free of charge.

Ordering example: Thermometer T4111, output -100 to +30°C

barometer wiring

Typical application wiring

Calculation of minimum power voltage Uss for proper operation:
Uss min> Uo min + Imax * Rz,
where: Uo min= 9 V
Imax... approximately 20 mA
Rz... sensing resistor (shunt)

Included accessory of thermometer:

Traceable calibration certificate from the manufacturer, instruction manual. Calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
Example of calibration certificate.

Free program TSensor for configuring of the transmitter is ready to download. SP003 cable for barometer adjustment via USB port is necessary to buy.

OPTIONAL ACCESSORY OF THERMOMETER
larger photo of thermometer cable SP003 cable for thermometer adjustment via USB port
sensor with connector - larger photo TxxxxL Transmitter version with watertight male connector IP67 Lumberg RSFM4 instead of cable gland for easy connection/disconnection of the output.
Specify please your order with letter L behind model code (e.g. TxxxxL)
thermometer connector K1427 Female connector ELKA 4012PG7 for TxxxxL transmitters with male connector Lumberg for easy connection/disconnection of the output.
Cable is easily connected to screw terminals of the connector. IP67 protection.
thermometer without display Transmitter version with blind lid without LCD.
Specify please the requirement in your order.
Pt1000 Temperature probe
Pt1000 Temperature probe
probes temperature probes with Pt1000 sensor without connector - probe marking is followed by symbol /0. Recommended is multi-purpose watertight probe Pt1000TG8/0 available with cable lengths 1, 2, 5, 10m
Larger photo of temperature transducer Dual Lock MD036 self adhesive Dual Lock for easy installation
Tool for easy transmitter connection - larger photo SP005 Tool for easy wire connection to terminals

data acquisition Transmitters are directly compatible with sixteen channel Comet data acquisition system MS.

Visit also available HUMIDITY, PRESSURE TRANSMITTERS.